- This gateway can read Modbus data from your Modbus RTU devices and publish it as BACnet MSTP data.
- It can also write to the Modbus RTU devices.
- This gateway can also do the reverse, read BACnet MSTP data and publish it as Modbus RTU data.
- It can also write to the BACnet MSTP devices.
In summary, this gateway can act as:
Master on the Modbus RTU network: Hence it is capable of reading data from the various Modbus slave devices and writing data to them if required.
Slave on the Modbus RTU network: You can use the gateway in this mode if you have a Modbus RTU master on the network which would be reading data from the gateway.
Client/Master on the BACnet MSTP network: Hence it is capable of reading data from the various BACnet MSTP devices and writing data to them if required.
Server/Slave on the BACnet MSTP network: The gateway can be configured to be a server of data values, hence another BACnet MSTP client can read data from the gateway and write data into the gateway.
QuickServer Key Features:
- BACnet Testing Laboratory (BTL) Mark
- Ability to interface up to 250 points of common BAS protocols
- Multi-configuration capability; specific configurations selectable via DIP switches or software
- Flat panel mount standard, DIN rail mount option
- DIP switches to select baud rate or node ID on the fly
BACnet MS/TP driver:
- Driver type: Client or Server
- Data Link layer: MS/TP master (Clause 9), baud rate up to 38.4 Kbps, MS/TP slave (Clause 9), baud rate up to 38.4 Kbps
- Connection type: RS-485 (two wire, half duplex)
- Baud rates: 9600, 38400, 76800
- BACnet COV support for fast data communication while reducing traffic over a BACnet network
- Data types supported:
- AI - Analog Input Object
- AO - Analog Output Object
- AV - Analog Value Object
- BI - Binary Input Object
- BO - Binary Output Object
- BV - Binary Value Object
- MI - Multi-state Input Object
- MO - Multi-state Output Object
- MV - Multi-state Value Object
Modbus RTU driver:
- Driver type: Client or Server
- Connection type: RS-232 or RS-485 (Two-wire, Half-Duplex)
- Baud rate: 110 - 115200, standard baud rates only
- Commands supported:
- 01 - Read Discrete Output Status (0xxxx)
- 02 - Read Discrete Input Status ((1xxxx)
- 03 - Read Output Registers (4xxxx)
- 04 - Read Input Registers (3xxxx)
- 05 - Force Single Coil (0xxxx)
- 06 - Preset Single Register (4xxxx)
- 15 - Force Multiple Coils (0xxxx)
- 16 - Preset Multiple Registers (4xxxx)
- BACnet is a trademark of ASHRAE
-We will configure the gateway for you based on your requirement and support you during commissioning of the gateway, so you do not have to worry about configuring the FieldServer gateway.
-However, it is very helpful to know how to configure the devices. All the required tools and supporting product manuals with be provided completely free of cost with your purchase.
-Configuration of the FieldServer is done using a '.csv' file. This file can be edited using any text editor (example Microsoft excel).
-In this file we need to enter information for the Client and Server side interfaces of the FieldServer. This includes but is not limited to:
Node ids of the slave devices
IP addresses/device address of the slave devices
Baud rate, parity, stop bits for serial communication
Scan rates
- And finally we need to create an internal mapping that would map each data value read on the client side to a data value on the server side.
-For detailed information on configuration please get in touch with us and review the configuration manual on top of this page