- This gateway can read Modbus data from your Modbus RTU devices and publish it as Modbus TCP data.
- It can also write to the Modbus RTU devices.
- This gateway can also do the reverse, read Modbus TCP data and publish it as Modbus RTU data.
- It can also write to the Modbus TCP devices.
In summary, this gateway can act as:
- Master on the Modbus RTU network: Hence it is capable of reading data from the various Modbus slave devices and writing data to them if required.
- Slave on the Modbus RTU network: You can use the gateway in this mode if you have a Modbus RTU master on the network which would be reading data from the gateway.
- Master on the Modbus TCP network: Hence it is capable of reading data from the various Modbus TCP devices and writing data to them if required.
- Slave on the Modbus TCP network: The gateway can be configured to be a server of data values, hence another Modbus TCP client can read data from the gateway and write data into the gateway.
QuickServer Key Features:
- Ability to interface up to 250 points of common BAS protocols
- Multi-configuration capability; specific configurations selectable via DIP switches or software
- Flat panel mount standard, DIN rail mount option
- DIP switches to select baud rate or node ID on the fly
Modbus TCP driver:
- Driver type: Client or Server
- Connection type: Internet Protocol (IP), 10/100BaseT
- Commands supported:
- 01 - Read Discrete Output Status (0xxxx)
- 02 - Read Discrete Input Status ((1xxxx)
- 03 - Read Output Registers (4xxxx)
- 04 - Read Input Registers (3xxxx)
- 05 - Force Single Coil (0xxxx)
- 06 - Preset Single Register (4xxxx)
- 15 - Force Multiple Coils (0xxxx)
- 16 - Preset Multiple Registers (4xxxx)
- EX - Exception Status
- FF - FIFO
- Data Types
- ASCII - 8-bit character
- Digital - Digital
- Float - 32-bit IEEE floating point
- Long - Unsigned 32-bit integer
- Signed - Signed 16-bit integer
- Slong - Signed 32-bit integer
- Unsigned - Unsigned 16-bit integer
Modbus RTU driver:
- Driver type: Client or Server
- Connection type: RS-232 or RS-485 (Two-wire, Half-Duplex)
- Baud rate: 110 - 115200, standard baud rates only
- Commands supported:
- 01 - Read Discrete Output Status (0xxxx)
- 02 - Read Discrete Input Status ((1xxxx)
- 03 - Read Output Registers (4xxxx)
- 04 - Read Input Registers (3xxxx)
- 05 - Force Single Coil (0xxxx)
- 06 - Preset Single Register (4xxxx)
- 15 - Force Multiple Coils (0xxxx)
- 16 - Preset Multiple Registers (4xxxx)
-We will configure the gateway for you based on your requirement and support you during commissioning of the gateway, so you do not have to worry about configuring the FieldServer gateway.
-However, it is very helpful to know how to configure the devices. All the required tools and supporting product manuals with be provided completely free of cost with your purchase.
-Configuration of the FieldServer is done using a '.csv' file. This file can be edited using any text editor (example Microsoft excel).
-In this file we need to enter information for the Client and Server side interfaces of the FieldServer. This includes but is not limited to:
Node ids of the slave devices
IP addresses/device address of the slave devices
Baud rate, parity, stop bits for serial communication
Scan rates
- And finally we need to create an internal mapping that would map each data value read on the client side to a data value on the server side.
-For detailed information on configuration please get in touch with us and review the configuration manual on top of this page